ASHRAE HBDP flashcards
ASHRAE HBDP · Build recall with a focused review session.
34 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Energy Use Intensity (EUI)
- Annual site energy consumed per unit of gross conditioned floor area, expressed in kBtu/ft2-yr or kWh/m2-yr. It enables comparison of buildings of different sizes and is the primary whole-building energy benchmark.
- Window-to-Wall Ratio
- The ratio of total glazed area to gross exterior wall area on a facade. It governs the trade-off between daylight and views versus solar gain and envelope heat loss.
- Solar Heat Gain Coefficient
- The fraction of incident solar radiation admitted through glazing, both directly transmitted and absorbed then released inward. Lower SHGC reduces cooling loads; it is specified per orientation.
- Thermal Bridge
- A path of high-conductance material that bypasses insulation, such as a slab edge or balcony. It raises effective assembly U-factor and must be broken with continuous insulation or structural isolators.
- Passive Design Load Reduction
- Reducing heating, cooling, and lighting loads through massing, orientation, envelope, and glazing before sizing active systems. Lower loads shrink every downstream equipment and operating cost.
- Daylight Autonomy
- The percentage of occupied hours when a target illuminance is met by daylight alone. It is preferred over static daylight factor because it reflects hourly availability and orientation.
- Envelope U-Factor
- The overall heat transfer coefficient of an assembly, in W/m2-K or Btu/h-ft2-F. It is the reciprocal of R-value and drives conduction losses through walls, roofs, and windows.
- Energy Balance Equation
- A building energy model must close: envelope, infiltration, internal, solar, and HVAC gains and losses sum to zero over the simulation period. Imbalance signals a modeling error.
- Degree-Day Method
- An estimate of annual heating or cooling energy from the difference between a balance-point temperature and outdoor temperature, summed over the year. Useful for screening, not design decisions.
- NMBE Calibration Criterion
- Normalized mean bias error, the average difference between modeled and measured energy normalized by measured data. Guideline 14 accepts about ±5% for monthly calibration data.
- CV(RMSE)
- Coefficient of variation of the root mean square error, measuring model scatter relative to measured mean. Guideline 14 accepts about ±15% for monthly data.
- Parametric Sensitivity Analysis
- Systematically varying design measures to rank annual energy savings per unit cost. Interactive effects mean savings from combined measures are not simply additive.
- Bin Method
- An energy estimate that bins hours by outdoor temperature and computes load at each bin. It approximates hourly simulation and is useful for economizer and part-load screening.
- Demand Charge
- A utility charge based on peak power (kW) during a billing period. A measure that cuts annual kWh can raise cost if it shifts load into on-peak hours.
- Weather Normalization
- Adjusting modeled or measured energy to a common weather year so that baseline and proposed cases, or different years, are compared on equal footing.
- Ventilation Rate Procedure
- ASHRAE 62.1 method setting outdoor air as per-person rate times occupants plus per-area rate times floor area, adjusted by zone air distribution effectiveness.
- CO2 Demand-Controlled Ventilation
- Modulating outdoor air based on measured indoor CO2, which tracks occupancy. It trims ventilation when occupancy is low but must not drop below code minimum rates.
- Operative Temperature
- The average of air temperature and mean radiant temperature, weighted by air speed. It is the temperature occupants actually experience and the basis of ASHRAE 55 comfort evaluation.
- PMV and PPD
- Predicted mean vote and predicted percentage dissatisfied. PMV estimates thermal sensation on a seven-point scale; PPD gives the fraction likely dissatisfied, with 80% acceptability a common target.
- Daylight Glare Probability
- A metric estimating the fraction of occupants disturbed by glare from windows. Values above roughly 0.35 to 0.40 indicate perceptible glare and warrant shading or light-redirecting design.
- MERV Rating
- Minimum Efficiency Reporting Value, a filter efficiency scale. MERV 13 and higher capture fine particulates, improving indoor air quality at a fan energy cost that must be balanced.
- Source Control vs Dilution
- Reducing pollutant emissions at the source, such as low-VOC materials and sealing, is more energy-efficient than diluting pollutants with additional outdoor air.
- Reverberation Time
- The time for sound to decay 60 dB in a room. Long reverberation impairs speech privacy and comfort; it is addressed alongside HVAC background noise in acoustic design.
- Owner's Project Requirements
- A written document stating the owner's functional needs, performance targets, and constraints. It anchors commissioning and is compared against the basis of design.
- Basis of Design
- The designer's record of assumptions, codes, and calculations that satisfy the owner's project requirements. Commissioning verifies that the installed systems match it.
- Functional Performance Testing
- Commissioning tests that verify systems under part-load, full-load, and failure modes. Testing only full-load operation misses most faults that occur in real operation.
- Retrocommissioning
- Applying the commissioning process to an existing building. It typically yields savings from correcting schedules, setpoints, and control sequences at low or no capital cost.
- Monitoring-Based Commissioning
- Using trend data and fault detection to continuously identify operational faults such as simultaneous heating and cooling, stuck valves, and schedule overrides after initial commissioning.
- IPMVP Options
- A framework for measurement and verification of savings. Options A through D differ in whether savings are measured at the whole-building or component level and how much is stipulated.
- Sequence of Operations
- The control document describing how equipment responds to conditions. Commissioning verifies it, and missing or unclear sequences are a leading cause of persistent energy waste.
- Cycles of Concentration
- The ratio of dissolved solids in cooling tower water to makeup water. Higher cycles reduce blowdown and makeup water but raise scaling risk and treatment requirements.
- Embodied Carbon
- Greenhouse gas emissions associated with material extraction, manufacture, transport, and disposal, expressed as kgCO2e. It is computed as material quantity times carbon factor.
- Cradle-to-Gate Boundary
- Life-cycle assessment stages A1 through A3, covering raw material extraction, transport, and manufacture up to the factory gate. It excludes construction, use, and end-of-life stages.
- Construction Waste Diversion
- The mass or volume of construction waste diverted from landfill divided by total waste generated. It is tracked during construction rather than estimated afterward.