Overload Trips on a 208 V Three-Phase Compressor
A 5-ton packaged unit with a 208 V three-phase scroll compressor (RLA 18.0 A, LRA 110 A) trips its internal overload after about 20 minutes of running on a 100°F day. Line voltage measured at the disconnect while the unit is running: L1-L2 = 210 V, L2-L3 = 205 V, L1-L3 = 196 V. Compressor current: L1 = 16.0 A, L2 = 15.2 A, L3 = 10.5 A. The contactor is pitted but pulls in cleanly, the run capacitor checks good, and the condenser coil is clean. The building has a large single-phase lighting load tapped off the same panel, and the unit was working 'fine' last summer.
1. Calculate the percent voltage unbalance and compare it to the NEMA limit. Show the formula.
Read the worked answer
Average voltage
(210 + 205 + 196) / 3 = 203.67 V
Maximum deviation from the average
|203.67 − 210| = 6.33 |203.67 − 205| = 1.33 |203.67 − 196| = 7.67 V ← largest
Percent unbalance
% unbalance = (max deviation / average) × 100 = (7.67 / 203.67) × 100 = 3.8%
NEMA limits three-phase motors to about 2% voltage unbalance. At 3.8% the motor is roughly double the limit, and the effect on current is disproportionate - this is the classic 'the voltage looks okay on a digital meter' trap, because 196 V on one leg still reads as a plausible number to a technician who is not averaging the three legs.
The 196 V leg is also the low-current leg, which confirms the problem is upstream of the motor rather than a motor winding fault.
2. Calculate percent current unbalance and explain what it means for this compressor thermally. Use the NEMA derating relationship to justify your recommendation.
Read the worked answer
Average current
(16.0 + 15.2 + 10.5) / 3 = 13.9 A
Maximum deviation
|13.9 − 10.5| = 3.4 A ← largest
Percent current unbalance
(3.4 / 13.9) × 100 = 24.5%
What this means
NEMA's derating curve for polyphase induction motors shows that a small voltage unbalance produces a much larger current unbalance - roughly a 6–10× multiplier at these levels. The standard derating is approximately:
- 1% voltage unbalance → 98% of rating
- 2% → 95%
- 3% → 88%
- 4% → ~82%
- 5% → 75%
At 3.8% voltage unbalance, the motor should be treated as capable of only about 82% of its nameplate rating - an 18 A compressor is effectively derated to roughly 15 A. Two legs are already at 15–16 A. The negative-sequence current caused by the unbalance produces a reversing field in the rotor, which heats the rotor and one set of windings without producing useful torque. That is exactly the failure mode that opens a scroll's internal overload after 20 minutes and, left alone, eventually grounds a winding.
Recommendation
Do not condemn the compressor yet. Fix the voltage first: the single-phase lighting load on the same panel is the prime suspect, along with a loose or corroded connection on L3 at the disconnect, contactor line side, or panel lug. Re-measure at the compressor terminals under load after correction, and add a phase monitor if the building's loads cannot be redistributed.
3. The customer wants the compressor replaced immediately because it 'keeps tripping.' How do you justify your plan, and what evidence would change your mind?
Read the worked answer
The case against replacing the compressor now
- The compressor's own overload is opening, which is protective behavior, not a failed winding. It has been doing its job.
- Current unbalance of 24.5% is a supply problem, not a motor problem. A new compressor installed on the same 3.8% unbalance will fail the same way, and the customer will have paid for a compressor and a repeat trip.
- The failure is repeatable and conditional (20 minutes, 100°F day, loaded operation), which is the signature of a thermal/electrical supply issue rather than a mechanical failure.
The plan
- With the unit off, check every connection from the panel through the disconnect, contactor line side, and compressor terminals for a high-resistance joint on the low leg. A voltage drop test under load on each leg is more telling than an open-circuit voltage reading.
- Re-measure voltage and current with the lighting load on and off to see whether the unbalance tracks the single-phase load.
- If the source is the utility or building distribution and cannot be corrected, install a phase monitor and derate/relocate load per NEMA guidance - and put that in writing to the customer.
Evidence that would change my mind and justify a compressor
- Normal voltage and current balance restored, or supply proven good, and the compressor still trips.
- Winding resistance to ground or an insulation test showing degradation.
- A winding resistance spread across the three phases beyond the manufacturer's tolerance.
- Low oil, acid, or a burned smell in the refrigerant circuit pointing to a mechanical/electrical failure inside the shell.
Only after the supply is proven good do we own the compressor. Until then we are replacing a part to fix a wire.