Quick reference

Planning, Layout, and Estimating

  • Heating and cooling loads are calculated room-by-room with ACCA Manual J using construction, window, orientation, infiltration, occupant, and climate inputs; equipment is then selected to meet the calculated load.

  • Nominal cooling airflow is about 400 cfm per ton (12,000 Btu/h); the design range is roughly 350–450 cfm/ton and must be checked against the equipment airflow table and sensible/latent load.

  • Sensible airflow: cfm = sensible Btu/h ÷ (1.08 × ΔT). Example: 24,000 Btu/h sensible with a 20°F ΔT requires 1,111 cfm.

  • Available external static pressure = blower rated external static minus pressure drops of filter, coil, electric heat, registers, grilles, and other devices; the remainder is the duct design budget.

  • Duct sizing uses ACCA Manual D with a friction rate derived from available static pressure and effective length; do not select duct size from cfm alone.

  • Total cooling capacity must meet sensible plus latent load; an oversized unit may satisfy sensible load before removing enough moisture.

  • Takeoffs list duct linear feet, fittings, insulation, sealant, hangers, and equipment; add a documented waste factor for cutoffs and field changes.

  • California Title 24 requires duct insulation, duct sealing, and duct leakage testing in specified climate zones; verify the applicable compliance form before layout.

Quick reference

Ductwork and Sheet Metal Fabrication and Installation

  • Smaller gauge number means thicker sheet metal; gauge is selected from SMACNA pressure-class tables using duct size, span, pressure, and support spacing.

  • Residential trunk design often uses about 0.1 in. w.c. friction loss per 100 ft of equivalent length; fittings add equivalent length and must be counted.

  • Seal all joints, seams, and penetrations in unconditioned spaces with mastic or listed foil tape; cloth-backed duct tape is not a permanent sealant.

  • Flexible duct must be fully extended, supported at manufacturer intervals, and kept free of sharp bends; compression or sag reduces airflow.

  • Rectangular equivalent diameter: De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25, where a and b are side dimensions in inches.

  • Use radius elbows or turning vanes instead of square elbows; abrupt turns increase pressure drop and turbulence.

  • Return air plenums must be sealed and must not use combustible materials or be penetrated by gas flues or electrical devices unless listed for the application.

  • Duct insulation R-value and vapor barrier placement depend on climate and location; in California attics, ducts are commonly specified at R-8 with a sealed vapor retarder.

Quick reference

Refrigeration Cycle and System Components

  • Superheat = actual suction temperature minus saturation temperature at suction pressure; typical target is 5–20°F depending on metering device and manufacturer data.

  • Subcooling = saturation temperature at liquid-line pressure minus actual liquid-line temperature; typical target is 8–15°F for many TXV systems.

  • A TXV maintains evaporator superheat by modulating flow; a fixed orifice relies on charge and operating conditions, so charge is set by superheat.

  • Compressors pump vapor; liquid slugging can damage valves and bearings, so low superheat and flooded starts must be corrected.

  • The evaporator absorbs heat and boils refrigerant; the condenser rejects heat and condenses refrigerant.

  • Saturation temperature is the boiling or condensing temperature at a given pressure; use a PT chart or gauge for the specific refrigerant.

  • Compression ratio = discharge absolute pressure ÷ suction absolute pressure; high ratios increase discharge temperature and reduce capacity.

  • Zeotropic blends have temperature glide; charge and service procedures must follow the refrigerant manufacturer's glide and fractionation guidance.

Quick reference

Heating Equipment and Heat Pump Systems

  • Furnace airflow: cfm = output Btu/h ÷ (1.08 × temperature rise); measured temperature rise must be within the nameplate range.

  • AFUE rates seasonal fuel efficiency; condensing furnaces typically exceed 90% AFUE and require a condensate drain and PVC venting.

  • Category IV furnaces operate with positive vent pressure and condensing flue gas; vent material, slope, and termination must follow the listing and code.

  • Heat pump COP = heat output in Btu/h ÷ electrical input in Btu/h; higher COP means more heat per unit of electricity.

  • The balance point is where heat pump capacity equals building load; below it, auxiliary heat stages operate.

  • Defrost is initiated by coil temperature, pressure, or time-temperature controls; auxiliary heat is usually energized during defrost to temper supply air.

  • Heat pumps need correct airflow and refrigerant charge; low airflow can cause high discharge temperature, icing, and compressor overload.

  • Combustion air and venting must be sized for all appliances in the space; backdrafting or spillage of flue gases is a safety hazard.

Quick reference

Electrical Systems, Motors, and Controls

  • Ohm's law: V = I × R. Single-phase power: P = V × I × power factor; resistive loads use P = V × I.

  • MCA is minimum circuit ampacity; MOP is maximum overcurrent protection. Wire ampacity must be at least MCA, and the breaker must not exceed MOP.

  • Voltage drop should generally not exceed 3% on a branch circuit and 5% total from service to load.

  • A disconnect must be within sight of and readily accessible from the equipment; grounding and bonding are required for safety.

  • Thermostat signals: R to W = heat, R to Y = cool, R to G = fan, R to O/B = reversing valve on heat pumps.

  • A run capacitor stays in circuit during operation; a start capacitor is switched out by a potential relay or centrifugal switch.

  • Capacitor microfarad reading should be within the manufacturer's tolerance, commonly about ±6%; a bulged capacitor should be replaced.

  • Contactors and relays use a low-voltage coil to control high-voltage contacts; pitted contacts cause voltage drop and intermittent operation.

Quick reference

Piping, Refrigerant Handling, and Brazing

  • Flow dry nitrogen through tubing while brazing to prevent internal oxidation; use a regulator and avoid excessive pressure.

  • Copper-to-copper joints can use silver-phosphorus brazing alloy without flux; copper-to-steel or brass joints require flux and proper cleaning.

  • Never use oxygen, air, or flammable gas to pressure-test a refrigerant system; use dry nitrogen and a pressure regulator.

  • Evacuate to 500 microns or lower, isolate the pump, and hold; a rising micron gauge indicates leak or moisture.

  • EPA Section 608 certification is required to service, repair, or dispose of equipment containing regulated refrigerants.

  • Install filter driers in the liquid line; use a suction-line filter drier after a burnout, then remove or replace it per manufacturer instructions.

  • Line-set size must follow the equipment manufacturer's table; undersized lines increase pressure drop and reduce capacity.

  • Insulate the suction line to prevent condensation and heat gain; do not insulate a liquid line unless required for freeze protection.

Quick reference

Testing, Evacuation, Charging, and Startup

  • Before charging, verify airflow, compressor rotation, electrical voltage, and stable operating conditions; charge adjustments require steady-state readings.

  • Fixed-orifice systems are charged by superheat using indoor wet-bulb and outdoor dry-bulb tables from the manufacturer.

  • TXV systems are charged by subcooling using liquid-line pressure and temperature, following the manufacturer's target.

  • Weigh-in charging is preferred when the total charge and line-set adjustment are known; use a scale accurate to the required tolerance.

  • Evacuation target is 500 microns or less for a tight system; hold the vacuum and watch for decay before opening valves.

  • External static pressure is measured with a manometer at the blower; total external static includes supply and return pressures.

  • Combustion analysis measures O2, CO2, CO, and flue temperature; use it to verify safe combustion and venting.

  • Startup records should include voltage, amp draw, capacitor microfarads, pressures, temperatures, superheat/subcooling, and temperature split.

Quick reference

Troubleshooting, Maintenance, and Repair

  • Low suction pressure with high superheat suggests undercharge, a restriction, or low evaporator airflow; verify airflow and pressure drop before adding refrigerant.

  • High suction pressure with low superheat suggests overcharge, oversized orifice, or excessive evaporator airflow; check metering device and charge.

  • High head pressure suggests dirty condenser, high ambient, noncondensables, or overcharge; check condenser airflow and subcooling.

  • Low head pressure suggests undercharge, low ambient, or inefficient compressor; compare suction and discharge pressures to expected values.

  • Ice on the evaporator coil usually indicates low airflow, low charge, or a restriction; correct the cause rather than only defrosting.

  • A compressor that will not start requires checking thermostat call, disconnect, breaker, contactor, capacitor, overload, and control lockout.

  • Excessive filter pressure drop reduces airflow; replace filters based on measured pressure drop or manufacturer schedule.

  • Preventive maintenance includes coil cleaning, belt and bearing inspection, electrical connection checks, condensate drain clearing, and charge verification.

Quick reference

Safety Practices and Code Compliance

  • Lockout/tagout isolates electrical and other hazardous energy; verify de-energization with a meter before touching conductors.

  • Refrigerant vapor can displace oxygen in low or confined spaces; ventilate and use a refrigerant monitor.

  • Never heat a refrigerant cylinder with an open flame; use warm water or a listed heater and follow cylinder pressure limits.

  • Recovery cylinders must not be filled above 80% of capacity by weight; use a scale and a cylinder rated for the refrigerant.

  • Use a nitrogen regulator and keep oil and grease away from oxygen fittings; oxygen can ignite hydrocarbons.

  • Combustion appliances require adequate combustion air and proper venting; use a CO monitor and check for spillage.

  • Arc flash and shock hazards require appropriate PPE and safe work practices; treat all conductors as energized until tested.

  • HVAC replacement and duct alterations may require permits and California Title 24 compliance documentation; verify before work begins.