CA C-20 HVAC flashcards
CA C-20 HVAC · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Manual J load calculation
- A room-by-room method that estimates heating and cooling loads from building construction, orientation, windows, occupants, and climate data to size HVAC equipment.
- 400 CFM per ton
- A nominal cooling airflow rule: one ton of cooling capacity (12,000 Btu/h) generally requires about 400 cubic feet per minute, though latent load and equipment data may require 350 to 450 CFM.
- Available static pressure
- The blower's rated external static pressure minus pressure losses from filters, coils, registers, grilles, and other components; it is the pressure budget used to select duct size and friction rate.
- Sensible heat airflow formula
- CFM equals sensible heat load in Btu/h divided by 1.08 times the entering-to-leaving air temperature difference; used to estimate required airflow for a space.
- Duct friction rate
- The pressure loss per 100 feet of duct, typically near 0.1 inch water column for residential design, used with an equivalent-length layout to size ducts from a duct calculator.
- SMACNA duct gauge
- A sheet metal thickness standard where smaller gauge numbers mean thicker metal; required gauge depends on duct size, span, pressure class, and support spacing.
- Duct leakage test
- A pressurization test that measures airflow lost through duct joints and seams at a specified pressure, commonly required by California Title 24 for new or altered duct systems.
- Flexible duct sag
- Flex duct should be supported so it stays straight and fully extended; excessive sag or sharp bends increase resistance and reduce delivered airflow.
- Superheat
- Suction line temperature minus the refrigerant's saturation temperature at the same suction pressure; it confirms vapor leaving the evaporator and protects the compressor from liquid.
- Subcooling
- Liquid line saturation temperature at the liquid pressure minus the actual liquid line temperature; it indicates how much liquid refrigerant has cooled below condensing temperature.
- TXV operation
- A thermostatic expansion valve modulates refrigerant flow to maintain a preset evaporator superheat, responding to bulb temperature and evaporator pressure.
- Compression ratio
- Discharge absolute pressure divided by suction absolute pressure; high ratios increase compressor heat and reduce capacity, often indicating low suction or high condensing pressure.
- Furnace temperature rise
- Supply air temperature minus return air temperature; it must fall within the furnace nameplate range and is used with Btu output to calculate airflow.
- Heat pump balance point
- The outdoor temperature at which heat pump heating capacity equals the building heating load; below it, supplemental or auxiliary heat is needed to maintain indoor temperature.
- Defrost cycle
- A heat pump mode that temporarily reverses refrigerant flow or stops the outdoor fan to melt frost from the outdoor coil, usually energizing auxiliary heat to avoid cold supply air.
- AFUE
- Annual Fuel Utilization Efficiency, a rating that estimates the percentage of fuel energy converted to useful heat over a heating season; higher values indicate greater efficiency.
- MCA and MOP
- Minimum Circuit Ampacity is the minimum wire ampacity required; Maximum Overcurrent Protection is the largest breaker or fuse allowed, both marked on the equipment nameplate.
- Ohm's law
- Voltage equals current times resistance (V = I × R); power in a resistive circuit equals voltage times current (P = V × I).
- Run capacitor
- A capacitor connected continuously in a motor circuit to improve phase angle, starting torque, and running efficiency; a bulged or failed capacitor can prevent the motor from starting.
- Thermostat R terminal
- The R terminal supplies 24-volt control power to the thermostat; connecting R to W calls for heat, R to Y calls for cooling, and R to G calls for fan operation.
- Nitrogen purge brazing
- A slow flow of dry nitrogen through the tubing during brazing prevents internal oxidation and scale, which can contaminate refrigerant circuits and damage valves and compressors.
- Evacuation hold test
- After evacuating to 500 microns or less, isolate the pump and watch the micron gauge; a rapid rise indicates a leak or moisture, while a slow rise may indicate normal outgassing.
- Recovery cylinder fill limit
- A refrigerant recovery cylinder must not be filled above 80 percent of its capacity by weight, leaving room for liquid expansion and reducing hydrostatic pressure risk.
- Weigh-in charging
- Charging refrigerant by weight using a scale and the manufacturer's required charge, adjusted for line-set length and component volume; it is the most accurate method when the full charge is known.
- Superheat charging method
- For fixed-orifice systems, adjust charge until measured superheat matches the manufacturer's target for current indoor wet-bulb and outdoor dry-bulb conditions.
- Subcooling charging method
- For TXV systems, adjust charge until measured subcooling matches the manufacturer's target, typically using liquid line pressure and temperature at stable operating conditions.
- Low suction, high superheat
- A diagnostic pattern often caused by undercharge, a restricted liquid line or metering device, or insufficient evaporator airflow; verify airflow and pressures before adding refrigerant.
- High head pressure
- A condition often caused by a dirty condenser coil, high outdoor ambient, noncondensable gas, or overcharge; check condenser airflow and subcooling before adjusting charge.
- Preventive maintenance visit
- A scheduled service that includes cleaning coils, changing filters, checking belts and bearings, tightening electrical connections, measuring amp draw, and verifying refrigerant charge and airflow.
- Lockout tagout
- A safety procedure that isolates electrical or other hazardous energy, applies a personal lock and tag, and verifies de-energization before service work begins.
- Refrigerant oxygen displacement
- Refrigerant vapor is heavier than air and can collect in low areas, displacing oxygen; use ventilation and a refrigerant monitor in confined spaces.
- Carbon monoxide testing
- Combustion analysis measures carbon monoxide and other flue gases; high CO or spillage indicates incomplete combustion or venting problems and requires correction.