CA C-20 HVAC · Work through your exam, one topic at a time.

All guide sections

Electrical Systems, Motors, and Controls

Circuits, motors, and control logic

Start with Ohm's law and power relationships for single and three phase, then apply them to actual parts: contactors and relays, heat sequencers, defrost boards, 24 V transformers, thermostats and the common wire, run and start capacitors, and motor overloads. Motor types you must recognize: PSC, ECM constant torque, ECM constant airflow, and three-phase induction. Synchronous speed equals 120 times frequency divided by the number of poles, so a four-pole motor at 60 Hz is nominally 1,800 rpm and about 1,725 rpm under load with slip.

Read the nameplate: RLA or FLA, LRA, minimum circuit ampacity, maximum overcurrent protection. Conductors, disconnects, and breakers are selected from those values, using NEC Article 440 for hermetic motor-compressors, not from habit.

Traps: substituting a run capacitor without matching microfarads; confusing locked rotor amps with running amps; condemning a compressor that is only humming because the capacitor or contactor failed; overlooking a rubbed control wire shorting to ground; forgetting to check the common side of the 24 V circuit when a thermostat display is blank.

Worked example: a 240 V single-phase unit drawing 12 A uses 2,880 VA. If the nameplate lists 24 A minimum circuit ampacity and 40 A maximum overcurrent protection, size the wire and breaker from those nameplate numbers; the observed amp draw is a performance check, not a sizing value.