Quick reference

General Electrical Knowledge and National Electrical Code Structure

  • Ohm's law: E = I × R. Power: P = E × I = I²R = E²/R, with E in volts, I in amperes, R in ohms.

  • NEC Chapters 1 through 4 apply generally; Chapters 5, 6, and 7 modify or supplement them; Chapter 8 (communications systems) is independent except where specifically referenced.

  • Articles 100 through 110 hold the definitions and general installation requirements, while Article 90 states the Code's scope and purpose.

  • The NEC is a minimum installation standard, not a design manual or instruction guide; the annexes are informational and are not enforceable unless adopted.

  • Balanced three-phase power: P = 1.732 × E(line) × I(line) × power factor.

  • Series resistances add directly; for parallel circuits 1/R_total = 1/R1 + 1/R2 + …, and the total is always less than the smallest branch resistance.

  • Conductor ampacities come from Table 310.16 with 60 °C, 75 °C, and 90 °C columns; the termination temperature rating limits the column that may be used, per 110.14(C).

  • Single-phase voltage drop: VD = (2 × K × I × L) ÷ circular mils, where K is about 12.9 for copper and 21.2 for aluminum.

  • Conductors installed in parallel must be 1/0 AWG or larger and identical in length, conductor material, size, and insulation characteristics (310.10(H)).

Quick reference

Wiring Methods, Materials, and Installation Requirements

  • Chapter 9 Table 1 limits raceway fill to 40 percent of interior cross-sectional area for three or more conductors, 31 percent for two, and 53 percent for one.

  • Box volume allowances from Table 314.16(B): 2.0 cubic inches per 14 AWG, 2.25 per 12 AWG, and 2.5 per 10 AWG conductor, with additional allowances for devices, clamps, and equipment grounds.

  • Section 110.26 requires a clear working space 3 feet deep, 30 inches wide, and 6.5 feet high in front of equipment likely to be examined while energized.

  • Nonmetallic-sheathed cable must be secured within 12 inches of each box and at intervals not exceeding 4.5 feet, and is not permitted in wet locations.

  • Dwelling receptacle spacing (210.52(A)): no point along a floorline may be more than 6 feet from a receptacle outlet, and wall spaces 2 feet or wider are counted.

  • The grounded conductor is identified by white, gray, or three continuous white stripes; the equipment grounding conductor is green, green with yellow stripes, or bare.

  • Support intervals: EMT within 3 feet of a box and at least every 10 feet; rigid metal and intermediate metal conduit at least every 10 feet.

  • Table 300.5 minimum cover: 24 inches for direct-buried cable generally, 18 inches for nonmetallic raceway, 12 inches for a 120-volt, 20-ampere GFCI-protected residential branch circuit.

  • Penetrations of fire-rated assemblies by cable or raceway must be sealed with a listed firestop method rated for the assembly.

Quick reference

Overcurrent Protection, Branch Circuits, and Feeders

  • Standard overcurrent device ratings (240.6(A)) include 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, and 200 amperes.

  • Small-conductor limits (240.4(D)): 14 AWG copper is protected at 15 amperes, 12 AWG at 20 amperes, and 10 AWG at 30 amperes unless a specific permission applies.

  • Next-size-up rule (240.4(B)): where conductor ampacity does not match a standard rating, the next higher standard device may be used up to 800 amperes, provided the load does not exceed the conductor ampacity.

  • Continuous loads: conductors and overcurrent devices are sized at not less than 125 percent of the continuous load plus 100 percent of the noncontinuous load (210.20(A), 215.3).

  • A feeder runs from the service equipment or a separately derived source to the final branch-circuit overcurrent device; the branch circuit runs from that device to the outlets.

  • GFCI protection is required for dwelling bathrooms, kitchens, garages, outdoors, unfinished basements, crawl spaces, and receptacles within 6 feet of sinks and laundry basins.

  • AFCI protection is required for 120-volt, 15- and 20-ampere branch circuits in dwelling units, including bedrooms, under 210.12.

  • Recommended voltage drop limits are 3 percent on a branch circuit and 5 percent total for feeder plus branch, per the informational notes to 210.19(A).

  • A multiwire branch circuit must have a means that simultaneously disconnects all ungrounded conductors at the point where it originates (210.4(B)).

Quick reference

Grounding, Bonding, and Electrical Safety

  • Section 250.50 requires all grounding electrodes present at a building to be bonded together into a single grounding electrode system.

  • A driven ground rod must be at least 8 feet long and driven the full 8 feet; if it does not measure 25 ohms or less to earth, one additional electrode must be added.

  • The main bonding jumper is installed only at the service or at a separately derived system; neutral-to-ground connections downstream of the service are prohibited.

  • Table 250.66 sizes the grounding electrode conductor from the largest ungrounded service-entrance conductor.

  • Table 250.122 sizes the equipment grounding conductor from the rating or setting of the overcurrent device protecting the circuit, not from conductor ampacity.

  • A Class A ground-fault circuit interrupter trips at 5 milliamperes plus or minus 1 milliampere and is used for personnel protection.

  • Metal water piping must be bonded, and a bonding jumper around removable fittings such as water meters maintains electrical continuity.

  • The equipment grounding conductor must form a permanent, low-impedance path capable of carrying fault current that will open the overcurrent device.

Quick reference

Motors, Controls, and Special Equipment

  • Branch-circuit conductors for a single motor must have an ampacity of at least 125 percent of the motor full-load current taken from Table 430.248 (single-phase) or 430.250 (three-phase).

  • Motor overload protection is generally sized at no more than 125 percent of the motor nameplate full-load amperes (430.32); up to 140 percent is permitted where the motor will not start.

  • Short-circuit and ground-fault protection sizing from Table 430.52: 250 percent of full-load current for an inverse-time breaker, 175 percent for a dual-element fuse, 300 percent for a nontime-delay fuse.

  • Each motor requires a disconnecting means within sight of and within 50 feet of the motor, or one that is capable of being locked in the open position (430.102).

  • Table 430.250 full-load current values are used for sizing conductors and short-circuit protection; the nameplate current is used for overload sizing.

  • A motor controller must have a horsepower rating not less than the motor it serves and must be capable of starting and stopping the motor.

  • Article 440 equipment uses rated-load current and branch-circuit selection current for hermetic refrigerant motor-compressors rather than the standard motor tables.

  • Motor control circuits tapped from the branch circuit require overcurrent protection sized per 430.72.

Quick reference

Idaho Electrical Licensing Statutes and Rules

  • Idaho's electrical licensing statutes are codified in Title 54, Chapter 10 of the Idaho Code, which establishes the Electrical Board and licensing requirements.

  • The Idaho Electrical Board operates within the Idaho Division of Occupational and Professional Licenses (DOPL), which processes applications, examinations, and renewals.

  • License categories include apprentice, journeyman, master, and limited or specialty electrician licenses, each with distinct scope and qualifications.

  • Idaho adopts the National Electrical Code by Board rule with state amendments; local authorities having jurisdiction issue permits and perform inspections.

  • Journeyman and master applicants must document qualifying work experience and pass a licensing examination.

  • Continuing education hours are required for license renewal, with the specific hours and cycle set by Board rule.

  • Apprentices must be registered with the state and work under the supervision of a licensed journeyman or master electrician.

  • Performing electrical work without a required license or permit is subject to civil and criminal penalties under Idaho law.