ID Electrician flashcards
ID Electrician · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's law
- The current through a conductor equals the voltage across it divided by its resistance, written as I = E / R, where E is in volts and R in ohms.
- NEC Chapter 8 scope
- Chapter 8 covers communications systems such as telephone, cable television, and network cabling, and it stands alone rather than being supplemented by Chapters 1 through 7.
- Article 100 definitions
- Article 100 defines standard Code terms such as branch circuit, outlet, and grounded conductor so that requirements are applied consistently throughout the NEC.
- Status of NEC annexes
- The annexes that follow Chapter 9 are informational only and are not enforceable as code requirements unless a jurisdiction specifically adopts them into law.
- Balanced three-phase power
- For a balanced three-phase load, power in watts equals 1.732 times the line voltage times the line current times the power factor.
- Parallel resistance rule
- For resistances in parallel, the reciprocal of the total equals the sum of the reciprocals of the individual resistances, and the total is less than the smallest branch.
- Box fill per 14 AWG
- Each 14 AWG conductor in a box counts as 2.0 cubic inches of volume under Table 314.16(B), before adding allowances for devices, clamps, and equipment grounds.
- Conduit fill 40 percent
- Chapter 9 Table 1 permits a raceway to be filled to 40 percent of its interior cross-sectional area when three or more conductors are installed.
- Working space requirements
- Equipment that may be examined while energized requires clear space in front of it that is 30 inches wide, 3 feet deep, and 6.5 feet high.
- NM cable support spacing
- Nonmetallic-sheathed cable must be secured within 12 inches of each box and at intervals not exceeding 4.5 feet along the length of the run.
- Dwelling receptacle spacing
- In dwelling units, receptacle outlets along walls must be arranged so that no point on the wall is more than 6 feet from an outlet.
- Grounded conductor identification
- The grounded, or neutral, conductor must be identified by a white finish, a gray finish, or three continuous white stripes along its entire length.
- Next size up rule
- Where a conductor's ampacity does not match a standard fuse or breaker rating, the next higher standard rating may be used, up to 800 amperes.
- Continuous load 125 percent
- Overcurrent devices and conductors serving continuous loads must be sized at not less than 125 percent of the continuous load plus 100 percent of the noncontinuous load.
- Standard overcurrent device ratings
- Standard ampere ratings include 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, and 100 amperes, as listed in Section 240.6(A).
- Small conductor protection limits
- Unless a specific permission applies, 14 AWG copper is limited to 15 amperes, 12 AWG to 20 amperes, and 10 AWG to 30 amperes of overcurrent protection.
- Class A GFCI trip level
- A Class A ground-fault circuit interrupter trips when it senses a ground-fault current of 4 to 6 milliamperes, providing protection for personnel.
- Feeder versus branch circuit
- A feeder is the set of conductors between the service equipment or derived source and the final overcurrent device; the branch circuit lies beyond that device.
- Ground rod 25 ohm rule
- A single driven ground rod must measure 25 ohms or less to earth; if it does not, a supplemental electrode must be installed and bonded to it.
- Equipment grounding conductor sizing
- Table 250.122 sizes equipment grounding conductors based on the rating or setting of the overcurrent device protecting the circuit, not on conductor ampacity.
- Main bonding jumper
- The main bonding jumper connects the grounded service conductor to the service equipment enclosure and grounding electrode conductor, and is installed only at the service.
- Separate neutrals in subpanels
- Neutral and equipment grounding conductors must be kept separate in panelboards and subpanels downstream of the service, with no neutral-to-ground bonding connections.
- Grounding electrode conductor sizing
- Table 250.66 sizes the grounding electrode conductor according to the size of the largest ungrounded service-entrance conductor supplied by the service.
- Motor overload protection
- Motor overload protection is generally sized at no more than 125 percent of the motor nameplate full-load ampere rating, as required by Section 430.32.
- Motor branch circuit conductors
- Branch-circuit conductors supplying a single motor must have an ampacity of at least 125 percent of the motor full-load current from Table 430.250.
- Motor disconnecting means location
- Each motor must have a disconnecting means within sight of and within 50 feet of the motor, or one that can be locked in the open position.
- Motor short-circuit protection
- Table 430.52 sizes motor short-circuit protection at a percentage of full-load current: 250 percent for an inverse-time breaker and 175 percent for a dual-element fuse.
- Article 440 equipment
- Article 440 covers hermetic refrigerant motor-compressors and air-conditioning equipment, which use rated-load current instead of the standard motor full-load current tables.
- Idaho Electrical Board
- The Idaho Electrical Board, within the Division of Occupational and Professional Licenses, administers electrician licensing and adopts the electrical code by rule.
- Idaho license categories
- Idaho issues apprentice, journeyman, master, and limited or specialty electrician licenses, each carrying its own experience, supervision, and examination requirements.
- Idaho electrical statutes
- Idaho's electrical licensing statutes are codified in Title 54, Chapter 10 of the Idaho Code, which establishes the Electrical Board and its licensing authority.
- Idaho code adoption
- Idaho adopts the National Electrical Code by Board rule with state amendments, while local authorities having jurisdiction issue permits and perform inspections of installations.