ID Electrician: Overcurrent Protection, Branch Circuits, and Feeders

ID Electrician · Work through your exam, one topic at a time.

All guide sections

Overcurrent Protection, Branch Circuits, and Feeders

Matching conductors to protection

Article 240 requires each conductor to be protected at its ampacity. Section 240.4(D) sets hard caps regardless of ampacity: 14 AWG copper at 15 A, 12 AWG at 20 A, and 10 AWG at 30 A for most circuits. Section 240.4(B) allows the next higher standard rating only when the ampacity does not match a standard size (240.6), the device is 800 A or less, the ampacity does not correspond to a standard rating, and the circuit does not supply multioutlet receptacles for cord-and-plug loads. Taps under 240.21 are the classic exception, and their length, ampacity, and enclosure rules must all be satisfied.

Branch circuits

Know the required circuits: a 20 A laundry branch circuit, two or more 20 A small-appliance circuits for the kitchen, and a 20 A bathroom circuit. Receptacle placement (210.52), lighting outlets (210.70), GFCI protection (210.8), and AFCI protection (210.12) are asked in nearly every exam. Feeder and service calculations live in Article 220 - general lighting demand factors, appliance demand, and the optional method for dwellings.

Traps

  • Making a breaker larger to stop tripping is never the answer; fix the load or the conductor.
  • Voltage drop recommendations (3% branch, 5% total) are informational, not enforceable.
  • A 240.4(B) next-size-up answer is wrong if the load is a multioutlet receptacle circuit.

Worked example

A feeder with a calculated load of 52 A and 6 AWG copper at 60 C (55 A ampacity) is protected by a 60 A breaker. Section 240.4(B) permits this because 55 A is not a standard rating, 60 A is the next standard size, and the device is under 800 A - assuming the circuit does not serve multioutlet receptacles.