Motors, Controls, and Special Equipment

Motor full-load current is not nameplate current

Article 430 requires motor branch-circuit conductors and protection to be based on the table full-load current (430.247 through 430.250), not the nameplate amperes. Nameplate values are used for overload protection. This single distinction generates more motor questions than any other.

The four sizing rules

  1. Branch-circuit conductors: 125% of table FLC (430.22).
  2. Overload protection: typically 125% of nameplate current for a marked motor above 1 hp (430.32).
  3. Short-circuit and ground-fault protection: from Table 430.52, commonly 250% of FLC for an inverse-time breaker or 175% for a dual-element fuse, with permitted increases if the device will not start the motor.
  4. Disconnecting means: within sight of the motor and controller, sized at least 115% of FLC (430.102, 430.110).

Controls and other equipment

Controllers must be capable of starting and stopping the motor and are located within sight unless the disconnect is lockable. Special-equipment articles frequently tested include 440 (air conditioning and refrigeration), 680 (pools and spas), 690 (solar photovoltaic), 700 (emergency systems), and 500/501 (hazardous locations, where the division and class drive every requirement).

Worked example

A 10 hp, 230 V, three-phase motor. Table 430.250 gives 28 A FLC. Branch-circuit conductors must carry 125% = 35 A, so 8 AWG copper is selected. Overload protection is set from the nameplate current times 125%. Branch-circuit protection on an inverse-time breaker may be 250% of 28 A = 70 A, the next standard size. Note the three different currents from one motor.